ANALISA KINERJA COOLING TOWER INDUCED DRAFT TIPE LBC-W 300 BERDASARKAN PENGARUH TEMPERATUR LINGKUNGAN

PERFORMANCE ANALYSIS OF COOLING TOWER INDUCED DRAFT LBC W-300 BASED ON DRY BULB TEMPERATURE

Author :
PRATIWI, NIMAS PUSPITO ( 2411106005 )




ABSTRAK

Telah dilakukan analisa kinerja cooling tower CT induced draft tipe LBC W 300 dengan metode kesetimbangan kalor dan massa. Analisa ini digunakan untuk menurunkan model matematis yang selanjutnya digunakan untuk mensimulasikan proses yang ada di cooling tower. Dari hasil simulasi didapatkan temperatur air keluaran cooling tower yang dipengaruhi oleh temperatur dry bulb dan wet bulb yang selalu berubah-ubah. Kinerja yang paling optimal di bulan September pukul 07.00 sebesar 27.91C saat temperature ambient dry bulb 26.6C. Pada musim hujan di bulan Februari 2013 kinerja cooling tower lebih maksimal. Temperatur air keluaran pada pukul 07.00 adalah 25.87C saat temperatur dry bulb 25.5C. Efisiensi cooling tower saat musim kemarau antara 41 sampai 72 sedangkan pada musim hujan efisiensinya 60 sampai 80. Kinerja cooling tower dapat ditingkatkan dengan cara meningkatkan kecepatan putaran fan sebesar 1550 rpm dan menurunkan laju aliran massa air menjadi 18.12 kgs sehingga daya fan dapat ditingkatkan sebesar 7.96 kW serta efisiensi cooling tower akan naik menjadi 81.63.


ABSTRACT

Performance analysis cooling tower induced draft LBC W- 300 has been done using heat and mass transfer analysis it is employed to derive the mathematic model then to simulate cooling tower process. The result shows that the output cooling tower temperature is influenced by fluctuating dry bulb and wet bulb temperature. The optimum performance is 27.91C at 7 am when dry bulb 26.6C during summer. During rainy season the performance is higher compared to summer. The temperature is 25.87C at 7 am when dry bulb 25.5C. The efficiency of cooling tower are 41 - 72 during summer and 60 - 80 during rainy season. The performance of cooling tower can be enhanced by increasing the velocity fan to 1550 rpm and decreasing the water mass flow rate to 18.12 kgs. So that the fan power can be enhanced to 7.96 kW and the efficiency of cooling tower can be optimized to 81.63



KeywordsCooling tower; temperatur ambient; kinerja
 
Subject:  Termodinamika
Contributor
  1. DR. Gunawan Nugroho, ST., MT
  2. Nur Laila Hamidah, ST., MT
Date Create: 30/01/2014
Type: Text
Format: pdf
Language: Indonesian
Identifier: ITS-paper-24121140005903
Collection ID: 24121140005903
Call Number: RSF 621.197 Pra a


Source
Paper and Presentation of Physics Engineering, RSF 621.197 Pra a, 2014

Coverage
ITS Coummunity

Rights
Copyright @2014 by ITS Library. This publication is protected by copyright and per obtained from the ITS Library prior to any prohibited reproduction, storage in a re transmission in any form or by any means, electronic, mechanical, photocopying, reco For information regarding permission(s), write to ITS Library




[ Download - Open Access ]

  1.  ITS-paper-34484-2411106005-paper.pdf - 388 KB
  2.  ITS-paper-34484-2411106005-presentation.pdf - 1941 KB




 Similar Document...




! ATTENTION !

To facilitate the activation process, please fill out the member application form correctly and completely

Registration activation of our members will process up to max 24 hours (confirm by email). Please wait patiently

POLLING

Bagaimana pendapat Anda tentang layanan repository kami ?

Bagus Sekali
Baik
Biasa
Jelek
Mengecewakan





You are connected from 35.175.248.25
using CCBot/2.0 (https://commoncrawl.org/faq/)



Copyright © ITS Library 2006 - 2019 - All rights reserved.
Dublin Core Metadata Initiative and OpenArchives Compatible
Developed by Hassan