Posted by tondoindra@gmail.com at 15/03/2016 14:39:14  •  643 Views


DESIGN LEVEL CONTROL SYSTEM ON THE STEAM DRUM USING CONTROLLER PID IN PT INDONESIA POWER UBP SUB UNIT PERAK-GRATI

PERANCANGAN SISTEM PENGENDALIAN LEVEL PADA STEAM DRUM DENGAN MENGGUNAKAN KONTROLER PID DI PT INDONESIA POWER UBP SUB UNIT PERAK-GRATI

Author :
APRIANSYAH, RIAN ( 2407100089 )




ABSTRAK

Steam Drum merupakan bagian penting dalam proses pembangkit energi listrik di PLTU. Dalam steam drum level air dijaga pada kondisi NWL Normally Water Level agar menghasilkan fluida cair yang berkualitas. Oleh karena itu diperlukan pengendalian level menggunakan metode tuning PID Zigler Nichols pada steam drum untuk meminimalkan kerusakan pada perusahaan dengan cara memodelkan terlebih dahulu kemudian melakukan uji performansi dan uji set point. Untuk mendapatkan parameter tuning PID dilakukan uji open loop yang nantinya akan mendaptkan nilai Kc 964I 964D dari masingmasing controller. Untuk nilai Kc 964I 964D dari LIC-100 PID sebesar 0.194601581 70 17.5 dan untuk PI nilai Kc dan 964I sebesar 0.145951186 dan 116.6666667. Dari nilai parameter tuning akan dilakukan uji set point dan performansi. Adapun nilai uji set point yang didapatkan sebesar 55.4219 untuk 5 60.8433 untuk 10 dan 66.2617 untuk 15. Sedangkan untuk nilai penurunannya sebesar 44.5869 untuk -5 39.1637 untuk -10 dan 33.7467 untuk -15. Terlihat bahwa untuk uji kenaikan semakin besar kenaikannya maka semakin besar pula nilai persentasenya. Begitu pula dengan penurunan yang semakin kecil nilai penurunannya maka semakin kecil nilai persentasenya. Untuk uji performansi didapatkan nilai IAE terbesar berada pada cascade 15 sebesar 43058.04 dan untuk tanpa cascade didapatkan nilai IAE sebesar 70384.02. Selain itu juga didapatkan nilai max. overshoot terbesar berada pada cascade 5 sebesar 8.438 dan untuk tanpa cascade didapatkan nilai max. overshoot sebesar 18.558 pada 15.


ABSTRACT

Steam Drum is an important part in the process of generation of electrical energy in PLTU. In the steam drum water level maintained at NWL conditions Normally Water Level in order to produce a quality liquid fluid. Therefore we need a level control using PID tuning method Ziegler Nichols on the steam drum to minimize damage to the company by way of modeling first then do a performance test and set point test. To get the tuning PID parameters conducted open loop test which will get the value of Kc 964I 964D of each controller. For the value of Kc 964I 964D of LIC-100 PID by 0.194601581 70 17.5 and PI values for Kc and 964I by 0.145951186 and 116.6666667. Of the value of tuning parameters will be conducted test set point and performance. The test set point value obtained by 55.4219 to 5 60.8433 to 10 and 66.2617 to 15. As for the value decline of 44.5869 on -5 39.1637 on - 10 and 33.7467 on -15. Showed that to test the increase the greater the increase the greater the percentage value. Similarly the smaller the decline value the smaller the percentage value. To test the performance of the largest IAE values obtained are in cascade 15 at 43058.04 and without cascade for IAE values obtained at 70384.02. It also obtained the value of max. largest overshoot is in the cascade 5 at 8438 and for the max value obtained without cascade. overshoot of 18 558 at 15.



KeywordsSteam Drum, Tuning PID Zigler Nichols, Level
 
Subject:  Steam
Contributor
  1. Hendra Cordova ST. MT.
Date Create: 15/03/2016
Type: Text
Format: PDF
Language: Indonesian
Identifier: ITS-paper-24121150008674
Collection ID: 24121150008674
Call Number: RSF 629.831 2 Apr p


Source
Paper And Presentation Of Physics Engineering RSF 629.831 2 Apr p, 2016

Coverage
ITS Community

Rights
Copyright @2016 by ITS Library. This publication is protected by copyright and per obtained from the ITS Library prior to any prohibited reproduction, storage in a re transmission in any form or by any means, electronic, mechanical, photocopying, reco For information regarding permission(s), write to ITS Library




[ Download - Open Access ]

  1.  ITS-paper-40781-ITS-paper-40781-2407100089-paper.pdf - 465 KB
  2.  ITS-paper-40781-ITS-paper-40781-2407100089-presentation.pdf - 532 KB




 Similar Document...




! ATTENTION !

To facilitate the activation process, please fill out the member application form correctly and completely

Registration activation of our members will process up to max 24 hours (confirm by email). Please wait patiently

POLLING

Bagaimana pendapat Anda tentang layanan repository kami ?

Bagus Sekali
Baik
Biasa
Jelek
Mengecewakan





You are connected from 18.215.33.158
using CCBot/2.0 (https://commoncrawl.org/faq/)



Copyright © ITS Library 2006 - 2020 - All rights reserved.
Dublin Core Metadata Initiative and OpenArchives Compatible
Developed by Hassan